Add to Cart
NO. | Items | Characteristics | Testing Methods | |
1 | Nominal Voltage | 76.8V | Follow GB/T18287-2013> | |
2 | Nominal Capacity | 40Ah | Follow | |
3 | Minimum Capacity | 38Ah | Follow | |
4 | Battery internal Impedance | Internal Impedance≤150mR | Internal Impedance Testing Machine(1kHz ) | |
5 | Shipment Voltage | 76.8~81.6V | Multi-meter | |
6 | Dimension | Length | 530x240x222mm | Vernier caliper |
Width | ||||
Height | ||||
Gross weight | Approx. 27kg | electronic scale | ||
7 | Working Temperature | Charge | 0~45℃,45~85%RH | Temperature & Humidity Instruments |
Discharge | -20~55℃,45~85%RH | |||
8 | Storage Temperature & Humidity Range | Short: above one month | -20~+55℃,45~85%RH | Temperature & Humidity Instruments |
Medium: above three months | 0~+45℃,45~85%RH | |||
Long:above one year | +5~+30℃,45~85%RH | |||
9 | Allowed maximum continuous charge current | 40A | Multi-meter | |
10 | Allowed maximum continuous discharge current | 50A | 170A(8S) | |
11 | Allowed maximum reverse charge voltage | NO Allowed | / | |
12 | Allowed maximum charge voltage | 87.6±0.2V | Multi-meter | |
13 | Discharge cut-off voltage | ≤65V | Multi-meter |
No. | Items | Standards | Testing Methods | |
1 | Vibration Testing | The appearance of battery should not leakage, break or explosion | Fix a charged battery on a vibrating table, vibrate it for 90 minutes in three mutually perpendicular directions at the 0.8mm resonance. The frequency is to be varied at the rate of 1hz/min between 10 and 55 hertz. | |
2 | High Temperature Discharge Testing | The battery should be no remarkable breakage, distortion. Discharge time should not less than 255mins | Place a full charged battery under the environments of 55℃ for 2 hours. Discharge it at the current of 200mA to the cut-off voltage. Then keep it at 20℃±5℃ for 2 hours. | |
3 | Low Temperature Discharge Testing | The battery should be no remarkable breakage, distortion. Discharge time should not less than 180 minute | Place a full charged battery under the environments of -20℃ for 15-24 hours. Discharge it at the current of 200mA to the cut-off voltage. Then keep it at 20℃±5℃ for 2 hours. | |
4 | Constant Humidity & Temperature Testing | The battery should be no remarkable breakage, distortion. Discharge time should not less than180mins | Place a full charged battery under the environments of 40℃ and 90% - 95%RH for 48 hours. And keep it in the room temperature for 2 hours. Then discharge it at the current of 200mA to the cut-off voltage. | |
5 | High & Low Temperature Storage | The battery should be no remarkable breakage, distortion. And charge/discharge normally | Place a full charged battery in a oven with 55±2℃ for2 hours, then keep it under 20±5℃ for 4hrs, then place it in a oven with -20±2℃ for 2 hours, then keep for 4 hours under 20±5℃, cycle as high temperature-normal temperature-low temperature-normal temperature-high temperature for 10 times |