Shenzhen Topband Battery Co., Ltd

A professional manufacturer of LiFePO4 battery / lithium iron phosphate, dedicated to designing, researching, manufacturing, and exporting LiFePO4 batteries( cell & pack & energy storage system) to

Manufacturer from China
Active Member
8 Years
Home / Products / UPS Rechargeable Batteries /

ESS UPS LiFePO4 Rechargeable Batteries 48V 400Ah RS485 Modbus Communication

ESS UPS LiFePO4 Rechargeable Batteries 48V 400Ah RS485 Modbus Communication

Ask Latest Price
Brand Name :Topband
Model Number :TB48400F-T105D
Certification :UL, MSDS
Place of Origin :China
MOQ :10
Price :Negotiable
Payment Terms :L/C, T/T
Supply Ability :3Gwh/year
Delivery Time :4weeks for samples; 6~8weeks for mass production
Packaging Details :standard export carton
Material :LiFePO4
Nominal Voltage :51.2V
Normal Capacity :400Ah
Internal resistance :≤60mΩ
Standard charge current :62.5A
Standard discharge current :200A
Dimension :600*600*1388mm
Weight :330Kg
Cycles :≥3500cycle (@DOD80% @0.33C)
Communication :RS485-Modbus
Contact Now

Add to Cart

Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
View Product Description

Long Life Time LiFePO4 UPS Rechargeable Batteries 48V 400Ah

1. General Information

This specification defines the performance of rechargeable LiFePO4 battery pack TB48400F-T105D manufactured by SHENZHEN TOPBAND BATTERY CO.,LTD, describes the type, performance, technical characteristics, warning and caution of the battery pack. This system Include 4 pack modules, 1 control module, and 1 standard 19”cabinet.

2. Specification(@Battery initial Temp25±5℃)

NO. Items Criteria Remarks
2.1 Rated Capacity 400Ah
Minimum Capacity 392Ah
2.2 Energy 20.48kWh
2.3 Nominal Voltage 51.2V
2.4 Outgoing Voltage ≥51.2V
2.5 Internal resistance ≤60mΩ
2.6 Charge voltage 58.4±0.2V
2.7 Floating charge voltage 55.2±0.2V
2.8 Standard charge current 200A
2.9 Maximum charge current 200A
2.10 Maximum discharge current 200A
2.11 Pulse discharge current 300A/Continuous for 3s
2.12 Discharge cut-off voltage 32~40V
2.15 Dimension Length: 600±3mm
Width: 800±3mm
Height: 1388±3mm
2.16 Weight Approx: 330Kg

2.17

Operating Temperature Charging:0~45℃
Discharging:-20~60℃
Recommended operating temperature:15℃~35℃
2.18 Self-discharge rate Residual capacity:≤2%/month;≤12%/year
2.19 Storage Temperature & Humidity Range Less than 1 month:-20℃~45℃,45%RH~75%RH
Less than 3 months:-10℃~35℃,45%RH~75%RH

Recommended storage environment:

15℃~35℃,45%RH~75%RH

Long time storage:

If the battery need be stored for a long time, the voltage should be 52.8V (50%SOC), and stored in the condition as storage proposal. It need at least one charge & discharge cycle every six months.


3. Instructions
1. Energy storage system assembly
Step1: Fix control box on top board of the cabinet with four screws, and 4 modules on boards below;
Step2: Install the power cables and communication lines. As for details, connect the control box to modules blow with power cables enclosed, connect control box and 4 modules in series with communication lines;
2. Directions for use
Step1: Connect the system output in the back of the control box to a proper load with power cable enclosed;
Step2: Push the button in the front of the control box, the energy storage system will be start, and some information like voltage, current, SOC, and temperature will be shown on the screen.

4. Dimension:

ESS UPS LiFePO4 Rechargeable Batteries 48V 400Ah RS485 Modbus Communication

5. Transportation

² Based on the character of cell, proper environment for transportation of LiFePO4 battery pack need to be created to protect the battery.

² Battery should stay in the warehouse 15℃~35℃ where it’s dry, clean, shade, and well-ventilated.

² The battery should be stored in 50% SOC during transportation.

² The battery needs to be charged every 6 months if out of use

² Keep the battery against dropping, turning over and serious stacking during loading.

² Ensure the single 48V 100Ah battery module in the independent package and keep it face up.

6. Warning & Tips

² Please read and follow the specification and caution remarks on battery surface before use the battery. Improper use may cause heat, fire, rupture, damage or capacity deterioration of the battery. SHENZHEN TOPBAND BATTERY CO.,LTD. Describes is not responsible for any accidents caused by the usage without following our specification.

² The battery must be far away from heat source, high voltage, and avoid to be exposed in sunshine for a long time.

² Do not put the battery in a charger or equipment with wrong terminals connected.

² Never connect the positive and negative of battery with metal.

² Avoid excessive physical shock or vibration. don't hit, fall, stamp on the battery

² Without the permission of the manufacturer and guidance, forbidden to remove or to assemble the battery

² Do not use the battery mixed with other different manufacturers, type, or model batteries.

² Keep the battery against high temperature. Otherwise, it will cause battery heat, get into fire or lose some function and reduce the life.

² When battery run out of power, please charge your battery timely (≤15day).

² Please use the matched or suggested charger for this battery.

² If battery emits a peculiar smell, heating, distortion or appears any abnormity during working or storage, please stop using and take it out from the device.

² If the battery leaks and get into the eyes or skin, do not wipe, instead, rinse it with clean water and see doctor immediately.

² Please far away from children or pets.

² Do not put disuse battery into a fire or water.

7. Battery operation instruction

7.1 Do not surpass the largest charging current that the specification stipulated.

7.2 Do not surpass the highest limited voltage that the specification stipulated.

7.3 Charging temperature:within temperature scope that specification stipulated.

7.4 Charge with constant current, then with the constant voltage, no reverse charge, which is dangerous

7.5 Special note:

Short time doesn't affect the use of the battery overcharge too, but for a long period of time over discharge or over charge can affect the function of the battery failure, or the battery can't use permanent, appear serious safety hazards, need a long time floating please use the recommended floating model specification.

8. Other Chemical Reaction

Because batteries utilize a chemical reaction, battery performance will deteriorate over time even if stored for a long period of time without being used. In addition, if the various usage conditions such as charge, discharge, ambient temperature, etc. are not maintained within the specified ranges, the life expectancy of the battery may be shortened or the device in which the battery is used may be damaged by electrolyte leakage. If the discharge time is much shorter than the normal after fully charged, even battery is charged correctly, and this may indicate it is time to change the battery.